Site Sentinel
®
16 Installation and Operation Manual
SETUP
Silence Sensor
Label: Used to identify the monitoring source.
Alarms Enter: This option enables the email alarms if the input source is
measured less than the Trip Level.
Alarms Exit: This option enables the email alarms when the input source is
measured as greater than or equal to the Trip Level
Email Addresses: This allows you to configure up to 8 emails to be sent when-
ever the input enters or exits an alarm.
Log Device: This enables the email logging of this device.
Delay Time: The delay is in (0 to 999) seconds. This option specifies the
wait time from when a value is out of range before an alarm
is activated.
Restore Time: The restore delay in (0 to 999) seconds. The input source
must be good for this amount of time before the alarm is
cleared.
Trip Level: Value from -25db to -35db below reference in 1db steps when
input source is considered to be in an alarm condition.
NOTE: After any item has been changed, you MUST press the “Save Settings”
button for your changes to be saved.